Relay protection tester 80 questions quiz answer

1. Why do we need to install a negative sequence voltage blocking device for the demagnetization protection of the generator?

Answer: The demagnetization protection of the generator may have to act when the voltage transformer breaks one phase or breaks the two phases and the system is asymmetric. In order to prevent the mis-magnetization protection from malfunctioning under the above conditions, a negative sequence voltage blocking device is installed to make the generator's demagnetization protection when the generator is really demagnetized, which reflects the de-magnetized relay action and the negative-sequence voltage blocking relay does not act.

2. What is the reactance transformer and why does the reactance transformer have an air gap?

A: The reactance transformer is a transformer with a primary winding connected to a current source (ie, input power supply) and the secondary winding is close to an open circuit state (ie, output voltage). Its reactance value (called transfer impedance) is the excitation reactance. Because it is required that the excitation reactance Ze should be small and have good linear characteristics, there must be a gap in the magnetic circuit. The excitation impedance Ze of the reactance transformer is basically reactive, so U2 leads the primary current I1 by approximately 90°.

3. What are the main differences between current transformers and current transformers that convert current into voltage in relay protection devices? How does the former make I1 and U2: in phase and the latter makes I1 and U2 reach the required phase?

A: The main difference is in the core structure, TA no air gap, and DKB has an air gap, open circuit excitation resistance TA is large and DKB is small; in the phase of primary current and secondary voltage, TA is in phase, DKB primary current is behind secondary voltage 90°; TA secondary voltage is taken from the voltage drop across the load resistor R. To achieve the same phase and appropriate capacitance, DKB can connect the variable resistor in parallel with the secondary coil. * Change the resistance to obtain the required phase.

4. Why should the generator be equipped with negative sequence current protection?

Answer: When an asymmetric short-circuit or three-phase asymmetrical operation occurs in the power system, there is a negative sequence current in the stator winding of the generator. This current generates a reverse rotating magnetic field in the air gap of the generator, which is twice the synchronous speed with respect to the rotor. As a result, a frequency-doubling current occurs in the rotor component. This current causes local burns in certain parts of the rotor where the current density is high. In severe cases, the guard ring may be loosened by heat, causing significant damage to the generator. Another 100Hz alternating electromagnetic torque will act on the large rotor shaft and the stator frame, causing a frequency of 100Hz vibration. In order to prevent the occurrence of the above-mentioned hazardous generator problems, negative sequence current protection must be set.

5, by the A, C phase current transformer differential protection of the composition of the protection line, when the protected circuit occurs a variety of phase short-circuit fault, the three-phase short-circuit as a benchmark, the relative sensitivity of how?

Answer: Because the current flowing through the relay during the three-phase short-circuit is Ik=√3I(3), the current flowing through the relay when the two phases are short-circuited is Ik=2I(2)=2×(√3/2·I(3) ). The current flowing through the relay when the two phases of BC are short-circuited is Ik=I(2)=I(3). The current flowing through the relay when the two phases of AB are short-circuited is Ik=I(2)=I(3). Therefore, when the three-phase short-circuit sensitivity KS=1 is used as a reference, KS=1 when the AC phase is short-circuited and KS=1/2 when the AB and BC phases are short-circuited.

6. Why should bus protection devices be installed in the high-voltage power grid?

A: Although the probability of a short-circuit fault on the bus is less than the number of transmission lines, the bus is a meeting point for multiple components. If bus faults are not quickly removed, the accident will be expanded, or even the system will be destroyed, which will endanger the safe operation of the entire system. serious. In the double bus system, it is of great significance to selectively cut off the faulty busbars and ensure that the busbars continue to operate. Therefore, it is required to generally install bus protection devices in high-voltage power grids.

7. In the normally closed contact loop of the synchronous relay in the three-phase reclosing start circuit, why should the series check circuit have a voltage normally open contact?

Answer: The series KV normally open contact in the same period of reclosing the start circuit of the reclosing, the purpose is to ensure that there is a voltage on the line before the coincidence period coincides. In addition, under normal circumstances, due to some reason, in the case of no pressure overlap detection, Because the circuit breaker falls off automatically, the line voltage cannot be reclosed. At this time, if the string with KV normally open contacts in the same period of the start-up circuit is checked in parallel with the no-voltage start circuit, the start-up circuit in the same period can correct this erroneous trip. .

8. What are the conditions for quasi-synchronous periods and what are the consequences of unsatisfied conditions?

A: Quasi-synchronized parallel conditions are that the voltage of the generator to be connected and the voltage of the system are the same, the phases are the same, and the frequencies are the same.

When the above conditions are not satisfied, juxtaposition will cause an inrush current. The greater the difference in voltage, the greater the inrush current; the greater the difference in frequency, the shorter the period of the inrush current. Inrush currents are detrimental to both generators and power systems.

9. What is the maximum sensitivity angle of the directional impedance relay and why is it necessary to adjust its maximum sensitivity angle equal to the impedance angle of the protected line?

Answer: The impedance angle of the maximum operating impedance (amplitude) of the directional impedance relay is called its maximum sensitivity angle φs. When the phase-to-phase short circuit occurs in the protected circuit, the angle between the short-circuit current and the voltage at the relay installation is equal to the impedance angle φL of the circuit. When the line is short-circuited, the directional resistance relay measures the impedance of the impedance, φm, equal to the impedance angle of the line, φL. To make the relay work in the most sensitive state, the maximum sensitivity angle φS of the relay is required. Equal to the impedance angle of the circuit to be protected, φL.

10. What is the voltage transformer reverse charging and what is the effect on the protection device?

Answer: The charging of busbars that are not energized through the secondary side of the voltage transformer is called reverse charging. Such as 220kV voltage transformer, change ratio is 2200, even if the busbar is not grounded, its impedance (including bus capacitance and insulation resistance) is large, assuming 1MΩ, but the impedance seen from the secondary measurement of the voltage transformer is only 1000000/(2200)2=0.2Ω, almost short circuit, so the reverse charging current is larger (the reverse charging current is mainly determined by the cable resistance and the leakage resistance of the two voltage transformers), which will cause the secondary side of the voltage transformer during operation. If the small switch trips or the fuse blows, the protection device in operation loses voltage, which may cause the protection device to malfunction or refuse to move.

11. Why should the generator be installed with low-voltage blocking over-current protection? Why does this protection use the current transformer at the neutral point of the generator?

Answer: This is set as a differential protection of the generator or backup protection of the next component. It acts when the following two types of faults occur: (1) When an external short-circuit occurs, the protective device or circuit breaker of the faulty component refuses to act. Time. (2) When the fault is within the differential protection range of the generator and the differential protection rejects the action. In order for this protection to work after the generator is not connected to the bus after the generator has been pressurized or disconnected from the busbar (voltage not dropped), an internal short circuit will still work, so the neutral point of the generator should be used. Current transformer.

12. Why does a large-capacity generator adopt 100% stator grounding protection and explain the principle of 100% stator winding single-phase grounding protection for additional DC voltage.

A: The ground protection using the zero-sequence current and zero-sequence voltage principle can not achieve 100% protection range for the stator windings. There is a dead zone near the near-neutral point. In fact, large-capacity units are often due to mechanical Damage or water leakage in the water-cooled system may cause ground faults in the vicinity of the neutral point. If such failures cannot be detected in time, it may cause the fault to expand and cause serious damage to the generator. Therefore, 100% protection zone stator ground protection must be installed on large-capacity generators. The principle of 100% stator grounding protection of the additional DC power supply is shown in Figure F-1. When the generator is in normal operation, there is no current in the KA coil of the current relay and the protection does not act. When the stator winding of the generator is single-phase grounded, the DC voltage passes through the ground point of the stator loop and is added to the current relay KA, so that a current passes through the KA and acts and sends a signal.

13. Why large-capacity generators should use negative-sequence inverse-time overcurrent protection?

A: The asymmetry of the load or system causes a negative-sequence current to flow through the stator windings of the generator and a negative-sequence rotating magnetic field is established in the air gap of the generator, causing the rotor to induce twice the frequency of the current, causing the rotor to heat up. Because of the direct cooling type (water internal cooling and hydrogen internal cooling), a large generator requires a smaller volume increase than a larger capacity. At the same time, the thermal capacity margin of a large unit is generally lower than that of a large generator due to economic and technical reasons. Small units are small. Therefore, the negative sequence additional heating of the rotor should pay attention, the general trend is that the greater the capacity of the single machine, the smaller the value of A, the lower the ability of the rotor to withstand the negative sequence current, so we must particularly emphasize the negative sequence protection of large generators. The duration of the allowable negative sequence current of the generator is A=I2t. The larger the I2 is, the shorter the allowable time is, and the smaller the I2 is, the longer the allowable time is. Because of the inverse time characteristics of the generator to I2, negative sequence reverse time overcurrent protection should be used on large units.

14. Why should the generator excitation circuit be equipped with one-point grounding and two-point grounding protection?

Answer: The generator excitation circuit is grounded at one point. Although it will not form a fault current path, it will not cause direct damage to the generator. However, it is necessary to consider the possibility of the second point of grounding. Therefore, a signal of grounding protection is issued to strengthen the inspection. Surveillance. When the generator excitation loop occurs with two earth faults: 1 The rotor of the generator is burned due to the fault current flowing through the fault; 2 The symmetry of the air gap of the generator is damaged, causing severe vibration of the generator; 3 The rotor slowly deforms to form an eccentricity, further exacerbating the vibration. Place two points of ground protection after one point of grounding, so that when two points of grounding occurs, it will stop after a delay.

15. What is the role of the longitudinal differential protection and horizontal differential protection of the generator and the protection scope? Is it possible to replace each other?

Answer: Diffusion protection is the most effective method of protection against internal short-circuit fault protection of the generator and is the main protection against short-circuits between generator stator windings.

The horizontal differential protection is to protect the stator winding of the generator from a phase-to-turn short circuit and the inter-turn short circuit protection between the two parallel branches of the same phase. For generators with a star connection and two parallel leads per phase, the generator must be installed. Set the horizontal difference protection. When the phase windings near the stator windings or near the neutral point are short-circuited, the current in the two neutral point connections is small, and the horizontal differential protection may not operate, and the dead zone may reach 15% to 20%), so it cannot replace the longitudinal differential. protection.

16, negative sequence current relay, when the two primary winding or secondary winding of the reactance transformer and the corresponding polarity of the winding of the intermediate converter is reversed, what will happen and how to prevent it?

Answer: Negative sequence current relay reactance Transformer When the primary or secondary windings are connected to the opposite polarity of the intermediate converter winding, the negative sequence relay will become a positive sequence relay. After the relay protection is put into operation, no asymmetry fault occurs, but if the load current reaches a certain value, it will malfunction. In order to ensure the correct connection of the negative sequence current relay and prevent the above situation, the following measures must be taken:

(1) Pass the three-phase power supply to check the setting of the negative sequence current relay.

(2) When testing with a single-phase power supply, the relative polarity should be measured in accordance with the principle of the negative-sequence filter, so that it meets the requirements, and the load current must be used for inspection. After confirming that the wiring is correct, it is put into operation.

17. Why is 220kV and above systems equipped with circuit breaker failure protection and what is its role?

Answer: The transmission line above 220kV generally has large power and long transmission distance. To improve the transmission capacity of the line and the stability of the system, phase-breaking circuit breakers and rapid protection are often used. Because the circuit breaker has the possibility of operation failure, when the circuit fails and the circuit breaker refuses to move, it will pose a great threat to the power grid. Therefore, the circuit breaker failure protection device should be installed, and the circuit breaker that will selectively reject the failure will be opened. The circuit breaker of the bus where the device is located (connected) is disconnected to reduce equipment damage, reduce the scope of power outage, and improve the safety and stability of the system.

18. Why does the negative sequence starting element in distance protection change to a three-phase output type?

A: Because the three-phase negative sequence current relay has a small ripple coefficient after three-phase full-wave rectification, the required filter capacitance is small, and the reaction speed is fast. Especially when the three-phase symmetrical short circuit occurs, the DC component in the short-circuit current can be fully utilized. Ensure that the device can operate. In addition, when the system oscillates and asymmetrically operates, the DC voltage of unbalanced voltage is output, and the ripple factor is small. After the differential circuit, the voltage of the actuator is low, so that it has a higher anti-vibration capability.

19. What are the requirements for WXB-11 microcomputer protection AC current loop wiring?

Answer: Microcomputer protection is different from other types of protection devices because it is based on computer program operations to determine internal and external faults and types of faults. Therefore, if the current loops of IA, IB, and Ic are connected to the positive polarity to protect the polarity of the microcomputer, then 3I. It must also be connected to the positive polarity to protect the polarity of the zero-sequence loop of the microcomputer. No reverse polarity access is allowed. Otherwise, when an internal fault occurs, the input data and the protection program do not correspond. It will be judged as an AC data acquisition system fault. The protection device is locked, causing the protection device to refuse to act when an internal failure occurs.

20. What are the advantages of the oscillation locking device constructed by using the negative sequence plus the zero-sequence current increment principle?

Answer: The oscillation blocking device activated by the negative sequence plus zero-sequence current increment can better distinguish the oscillation and the short circuit, and can prevent the protection from malfunction due to the increase of the imbalance output of the negative sequence current filter when the system oscillates. It can also prevent unbalanced output of the filter when the line is not transposed, three-phase unbalanced, harmonic components, and non-full-phase operation are unbalanced. The locking device adopts the design principle of "non-stopping oscillation and unblocking" so that the protection will not malfunction due to the long duration of oscillation. Because the protection is only put into operation for a short time after the operation of the actuator, the system will operate without causing protection malfunction. In addition, this type of oscillating locking device also has a higher sensitivity and a faster operating speed, and thus has been widely used.

21, direction of over-current protection Why must start with the phase mode?

Answer: Directional over-current protection adopts the “phase-by-phase” wiring method in order to avoid misoperation of the device when the two-phase short circuit occurs in the opposite direction. For example, when the BC phase short-circuit occurs in the reverse direction, the relay in the phase A direction of the line will operate in the positive direction due to the load current. If the phase is not started at this time, when the C-phase current element is activated, it will cause the device to malfunction; Phase start wiring, although the A-phase direction relay operates, but the A-phase current element does not move, and the C-phase current element operates but the C-phase direction relay does not operate, so the device will not malfunction.

22, what is the connection coefficient of the current transformer? What is the effect of the wiring factor?

Answer: The ratio of the current through the relay and the secondary current of the current transformer is called the wiring coefficient of the current transformer, that is, the current in the Ik-I flow relay of the type Kc=Ik/I2; 12--the current transformer of the current transformer The secondary current connection coefficient is an important parameter in the relay protection setting calculation. The wiring factor must be taken into consideration when calculating the action values ​​of various current protection measurement components.

23, what is the high frequency blocking distance protection?

Answer: The basic principle of high-frequency blocking distance protection is to use â–³I2 â–³I. Incremental components act as starting components. They start high-frequency transceivers in the event of a fault, send high-frequency blocking signals, and use distance-II or III-direction directional impedance relays as faulty power-discriminating components. If internal faults occur, both sides of the distance protection stage or The third segment measures the action of the component, stops the high-frequency blocking signal, and instantaneously trips off the fault. If an external fault occurs, the positive-direction side contacts the impedance relay in the II- or III-direction direction to stop the transmission, but the impedance element in the opposite direction does not operate, and the relay continues to send the protection to the opposite side of the latch. This not only has the function of high-speed protection across the line, but also has the function of distance protection II for adjacent backup protection. Its main disadvantage is that the high-frequency protection and distance protection wiring are not connected to each other for easy operation and maintenance.

24. How to check the resonant frequency of the series resonance filter?

A: Connect the filter to the wiring as shown in Figure F-3. The resistance R of the circuit should be such that the output of the oscillator does not exceed its rated capacity when the impedance Z of the filter is minimum. Then use a high internal resistance voltage meter to measure the voltage on R. The voltage of the fixed oscillator is 10V, change its frequency, when the tube voltmeter indicates maximum, the corresponding frequency is the resonance frequency of the filter.

25. What is the reaction to the imbalance of active power in the power system? How to deal with?

Answer: The excess active power in the system will cause the frequency to rise, and the lack of active power will cause the frequency to drop. The solution is to adjust the output of the generator through the frequency modulation unit. When the situation is serious, some generator sets or part of the load are cut off through the automatic device or on-duty personnel operation to balance the system power.

26. For 3U. What constitutes a protection test and what are the countermeasures?

A: There are the following countermeasures for the 3Uo protection test:

(1) The 3Uo loop cannot be confirmed by checking the 3Uo loop for unbalanced voltage.

(2) It is not possible to confirm the correctness of the polarity of the directional protection formed by 3Uo by using the “hexagonal” test method alone.

(3) Tests may be conducted on the overall composition including current and voltage transformers and their secondary circuit connection and directional components to confirm that the polarity of the entire set of directional protection is correct.

(4) The most fundamental method is to find out the polarity of the voltage transformer and current transformer, and the polarity of all the connections from the transformer terminal to the relay protection screen and the polarity of the zero-sequence direction relay on the screen. judgment.

27, What is the danger of the power of the power direction relay? How to eliminate the inductive power direction relay?

A: The power direction relay may have reverse and positive creep. Reverse creep will increase the operating power. Positive creep may cause the protection to malfunction. The method to eliminate the creep of the induced power direction relay is as follows:

(1) Turn the position of the core column.

(2) Move the relative position of the voltage coil.

(3) Connect the voltage coil to the positive or reverse polarity of the compensation coil in series.

(4) Move the pole position slightly without the coil.

28. Simulate the setting of the three-phase short-circuit test negative sequence current relays. Why is the test current √3 times the value of the negative-sequence current setting? Analyze the symmetric component method.

A: Decompose a set of three-phase asymmetrical currents of A, B, and C into positive, negative, and zero-sequence symmetrical components. The negative-sequence symmetrical component is I2=1/3 (IA+a2IB+aIc). For short circuit, there is IB=-Ic=Ik(test current), IA=0 and its phasor is shown in Figure F-4. From the figure, we know a2IB+aIc=√3Ik, so I2=1/3·Ik·√3=Ik/√3. Similarly, it can be deduced that when ABCA two-phase short circuit is I2=Ik/√3, that is, the test current is a negative-sequence current. 3 times.

29. What is the blocking angle of high-frequency protection?

A: As shown in Figure F-5(a), when a through fault occurs at point k, ideally IM and IN

180 degrees difference, the protection device does not operate. In fact, when the line is externally faulty, due to various factors, the phase angle difference between IM and IN is not 180°, and the signal received by the receiver has a discontinuous angle. According to the principle of phase difference high frequency protection, the protection device will act when the line breaks and the discontinuity occurs. For this purpose, the maximum possible discontinuity angle of external faults should be found out, and this value should be used for blocking so as to ensure that the protection does not malfunction when the line fails externally. This maximum discontinuity is called the difference in the blocking angle of the high-frequency protection. As shown in Figure F-5 (b>), the protection zone φop is (180°-β)> φop> (180°+β), and the blocking angle is β.

30. What regulations should be followed in the management of the operating procedures of microcomputer relay protection devices?

Answer: The management of the operating procedures of microcomputer relay protection devices should follow the following rules:

(1) All networks (provinces) shall coordinate the procedures for the unified management of microprocessor relay protection devices within the scope of direct jurisdiction. Each network (provincial) shall set up a relay protection laboratory. After the new procedure passes the full test of the laboratory, Allow to be put into operation in the field.

(2) The same type of microcomputer high-frequency protection program version at both ends of a line should be the same.

(3) The program change of the microprocessor relay protection device shall be strictly implemented according to the procedure notice issued by the professional department of the dispatching relay protection.

Relay Protection Knowledge Q & A Compilation is provided by the Department of Biotechnology of Yangzhou Tuopu Electric Technology Co., Ltd., Hotline for consultation, website:. . Com

31. What is the criterion for how to open the impedance relay of LFP-901A protection when it fails again in the non-full-phase operation?

Answer: Open by non-full-phase oscillation locking element:

(1) When the single-phase fault reoccurs in the non-full-phase operation, the phase-selection area is not opened when the phase-opening fault occurs.

(2) When a phase-to-phase fault occurs again in a non-full-phase operation, the power-frequency variation of the difference between non-faulty two-phase currents is measured, and is opened when the current suddenly increases to a constant amplitude.

32. What problems should be noticed in the inspection of microcomputer relay protection devices?

Answer: When testing the relay protection device of the microcomputer, in order to prevent damage to the chip, the following problems should be noted:

(1) The microcomputer relay protection screen (cabinet) should have good grounding, and the grounding resistance should meet the design requirements. When measuring the circuit parameters using an AC power source electronic instrument (such as an oscilloscope, a frequency meter, etc.), the measurement terminals of the electronic instrument and the power supply side should be well insulated, and the instrument housing should be grounded at the same point as the protection panel (cabinet).

(2) The electric soldering iron should not be used in the test. If a soldering iron must be used, a special soldering iron should be used, and the soldering iron should be grounded at the same point as the protective screen (cabinet).

(3) When touching the pins of the chip by hand, measures shall be taken to prevent the damage of the IC to the IC chip.

(4) Plug and pull plugs are allowed only after the DC power is disconnected.

(5) Pull out the chip application special extractor, insert the chip should pay attention to the direction of chip insertion, after the insertion of the chip should be confirmed by the second person after the confirmation, before the electricity can be tested or used.

(6) When measuring the insulation resistance, insert the card with IC chip (except optocoupler and power plug).

33. In a small ground current system, why is single-phase ground protection used only to signal in most cases and not to trip?

Answer: In the small grounding current system, the symmetry of the system voltage is not damaged when a phase is grounded, the current through the fault point is only the capacitive current of the system, or the residual current after the arc suppression coil is compensated, and the value thereof is very small. The impact on grid operation and users' work is small. In order to prevent a short-circuit fault from occurring when grounding occurs again, the protection device is generally required to issue a warning signal in time so that the on-duty personnel can handle it as appropriate.

What is the principle of line phase-to-phase short-circuit protection configuration in 34. 5kV neutral point ungrounded networks?

Answer: The principle of phase-to-phase short-circuit protection configuration is:

(1) When using two-phase current protection, the current transformer should be mounted on the same phase of each outgoing line (for example, phase A and phase C).

(2) The protection device adopts far-back-up mode.

(3) If the line short-circuit causes the voltage of the power bus for the power plant, the bus of the main power contact point, or the voltage of the important user bus to fall below 50% to 60% of the rated voltage, the fault should be quickly removed.

35. After the new installation and overhaul of the power transformer, why should the impact closing test be conducted before the official operation?

Answer: The power transformer after the new installation and overhaul must be subjected to the impact closing test before it is officially put into operation. This is to check the insulation strength and the mechanical strength of the transformer, and to inspect the performance of the differential protection from the excitation inrush current. The newly installed equipment should be impacted 5 times and the equipment should be impacted three times after overhaul.

36, what is the automatic load reduction AFL device according to frequency? What is its role?

A: In order to improve power quality and ensure the availability of power for important users, when the frequency drop occurs due to the lack of active power in the system, depending on the degree of frequency decrease, some unimportant users are automatically disconnected, and the frequency is prevented from decreasing so that the frequency can be reduced. Quickly restored to normal, this device is called automatic frequency-reducing device, referred to as AFL device. It can not only guarantee the power supply of important users, but also avoid the collapse of the system caused by the frequency drop.

37. The two-phase current difference wiring of a relay can not be used in the case of Y, d wiring transformers.

Answer: Transformers that cannot be used in Y, D wiring. The phase winding of the transformer Y side is subjected to the phase voltage, and the phase of the delta side receives the line voltage, so the number of turns of the side winding of the triangle NΔ=√3Ny, and the ratio Iy/IΔ=Ny/NΔ=√3, such as When mounted on the Y side and a two-phase short circuit occurs on the △ side (ab phase), the A- and C-phase currents on the Y-side are both 1/√3, so the relay does not move.

38. Why does the overcurrent protection setting take into account the relay's return coefficient and the current quick-break protection does not need to be considered?

Answer: The overcurrent protection's operating current is set to escape the maximum load current and generally protects adjacent equipment. In the event of an external short-circuit, the current relay may start, but after the external fault has been removed (the current is dropped to the maximum load current), it must be *returned, otherwise false tripping will occur. The purpose of considering the return coefficient is to ensure that the protection energy * can be returned in the above case. The operating value of the current quick-break protection is set according to the maximum short-circuit current avoiding the predetermined point, and its setting value is much larger than the maximum load current, so there is no problem of not returning under the maximum load current. Furthermore, once the instant current quick-break protection starts the crap trip, there is no midway return problem, so the current quick-break protection does not consider the return coefficient.

39. Some distance protection will not immediately malfunction when the secondary circuit of the voltage transformer is out of phase. Why is there still a need to install a voltage loop off-phase locking device?

A: At present, there are some new or modified distance protections. The starting circuit is blocked by a negative sequence current element. When the secondary loop of the voltage transformer is broken, although the impedance element will malfunction, because the negative sequence current element does not start, the protection device will not immediately cause a malfunction. But when the secondary circuit of the voltage transformer is out of phase and encounters a through fault, it will still malfunction, so it is also necessary to signal when the secondary circuit of the voltage transformer is out of phase, and the time is greater than the time delay of the third stage delay. Latch protection.

40. Some distance protection will not immediately malfunction when the secondary loop of the voltage transformer fails. Why do you still need to install a voltage loop phase-locking and locking device?

A: At present, there are some new or modified distance protections. The starting circuit is blocked by a negative sequence current element. When the secondary loop of the voltage transformer is broken, although the impedance element will malfunction, because the negative sequence current element does not start, the protection device will not immediately cause a malfunction. However, when the secondary loop of the voltage transformer is out of phase and a through fault is encountered, misoperation will still occur. Therefore, the secondary transformer of the voltage transformer will also be signaled when the secondary loop is out of phase, and will start after the delay time greater than the III. Latch protection.

41. Why is it that the resonant frequency of the wave trap is about 0.2 kHz lower than the frequency of use?

A: Due to the phase-coupled high-frequency channel, other devices connected to the bus line form an impedance to ground. This impedance is connected in series with the impedance of the line trap to form a shunt of the high-frequency signal channel, resulting in shunted losses. The amount of shunt loss depends on the phasor sum of the two impedances. Experience has shown that the bus-to-ground impedance is capacitive in most cases. In order to avoid a series resonance between the impedance of the busbar and the bus-to-ground capacitor, the reactive component of the impedance of the resistor is cancelled out, so that the branch impedance is drastically reduced and the shunt attenuation is reduced. Increasing, it is required to protect the use of the trap's resonant frequency is lower than the protection of the use of frequency of about 0.2kI-Iz, to ensure that the trap in the use of frequency capacitive, so as to obtain the maximum impedance of the trap.

42. How to adjust the resonance frequency and blocking frequency band of a single frequency wave trap?

Answer: Wire as shown in Figure F-8. The voltage of the fixed oscillator is a certain value, change the frequency, when U2 appears minimum Umin, this frequency is the resonant frequency, and then change the frequency, when the U2 reading is Umin value of the upper and lower frequency difference, that is, single-phase resistance The waveband of the wave filter is â–³F.

43. How to set the current control element in circuit breaker failure protection?

Answer: When the current control element is in the minimum operating mode, the local busbar is faulty, and when the fault current at the opposite end is the minimum, there should be enough sensitivity to set the current control element. After the disconnection of the busbar breaker, the current control element should be able to operate. The setting value of the current control element should generally be greater than the load current. If the load current cannot be avoided after the sensitivity is set, the sensitivity requirement should be met.

44. Why is a non-linear resistor R connected in parallel at the entrance of the transistor transmitter channel and two diodes of opposite polarity in parallel are connected in R?

A: A non-linear resistor in parallel with the channel population is to make the device immune to the impact of channel interference signals. Because of the large static capacitance of the nonlinear resistor, a single and a non-linear resistor has a certain bypass effect on the high-frequency signal, so that the output voltage is reduced. Therefore, in the non-linear resistor R, two parallel-connected diodes of opposite polarity are connected. This reduces the total capacitance in the loop because the total capacitance between the poles of the diode is much smaller than the static capacitance of the non-linear resistor. The purpose of the diode is to prevent the positive and negative direction of the interference pulse current from being absorbed by the nonlinear resistor.

45. What is the load regulation effect? ​​If there is no load regulation effect, what will happen to the system when there is a shortage of active power?

A: When the frequency decreases, the active power drawn by the load decreases. When the frequency increases, the active power drawn by the load increases. This phenomenon of changing the active power of a load with frequency is called a load regulation effect.

Because of the existence of the load regulation effect, when the frequency changes due to the power balance failure in the power system, the load power changes with it and plays a compensating role. If the frequency drops due to the lack of active power in the system, the corresponding load power will also decrease, and some active power shortages will be compensated, which may make the system stable at a lower frequency. If there is no load regulation effect, when the frequency of the active power shortage system drops, the power shortage can not be compensated and the new active power balance will not be reached, so the frequency will decrease until the system collapses.

46. ​​What happens to the distribution of zero-sequence current when a ground fault occurs in a large ground current system?

A: The distribution of the zero-sequence currents is only related to the system's zero-sequence network and has nothing to do with the number of power supplies. When increasing or decreasing the number of neutral grounded transformers, the system zero-sequence network will change, thereby changing the zero-sequence current distribution. When increasing or decreasing the number of generators connected to the busbar and the number of ungrounded neutral transformers, and the number of neutral-grounded transformers does not change, only the magnitude of the ground current is changed, regardless of the distribution of the zero-sequence current.

47. Why is it necessary to set up a three-hop circuit breaker in high-frequency protection with remote start?

A: (1) In the event of a fault in the area, the circuit breaker on one side trips first. If the circuit breaker is not stopped immediately, the transmitter will generate continuous high-frequency signals due to no operating current, and the receiving side of the opposite side will also receive continuous signals. The high-frequency signal is latched to protect the outlet and cannot be tripped.

(2) When manually or automatically reclosed to a permanent fault, because there is no closing on the opposite side, the remote starting circuit sends a high-frequency continuous wave, so that the side to be closed first is blocked and the protection is refused. In order to ensure that the two devices can be operated in the above situation, a circuit breaker tripping trip must be set.

48. Why does a large grounding current system not use three-phase and phase current protection and zero-sequence current protection, but uses zero-sequence current protection alone?

A: The phase-to-phase current protection of the three-phase star connection can also react to the grounding short circuit, but when it is used to protect the ground from a short circuit, the maximum load current must be avoided at the fixed value, and the user must press the power supply direction in the operation time. The ladder principle is gradually increased by a time difference. The zero-sequence current protection that specifically reacts to the ground short circuit does not need to be set in accordance with this principle. Therefore, it has high sensitivity and short operation time, and because the zero sequence impedance of the line is much larger than the positive sequence impedance, the protection of the zero sequence current protection The range is long, and it is easy to fit between the lower and upper levels of protection. Therefore, phase current protection and zero-sequence current protection are generally not used.

49. Why does the three current transformers that make up the zero-sequence current filter have the same characteristics?

Answer: The output current of the zero-sequence current filter is IK=(IA+IB+IC)/nTA=3I. ×1/nTA In the equation above, the excitation current of the current transformer is ignored. Consider the output current of the excitation current filter as IK = [(IA + IB + IC) - (IAe + IBE + ICe)] / nTA where Iae + IBa + ICe)] / nTA is called unbalanced current if the three phases Current transformer saturation program is different, asymmetry of the excitation current and some differences formed in the manufacturing, in the normal operation will appear larger unbalanced current. Especially in the transient process of phase-to-phase faults, the short-circuit current contains a large non-periodic component, causing the current transformer core to be heavily saturated and a large unbalanced current appears. In order to reduce the unbalanced current, it is necessary to make the magnetization curves of the three current transformers the same, and work in the unsaturated part, while also minimizing its secondary load, so that the three-phase current transformer load is balanced as much as possible.

50. How to use the method of disconnecting one phase of working voltage and verifying the correctness of the negative sequence power direction relay wiring by means of three working currents A, B and C respectively.

Answer: (1) Measure the correct phase of the load current and the corresponding operating voltage.

(2) Disconnect the voltage of one phase of the breaker and connect the terminal of the disconnected phase to UN to simulate the negative sequence voltage. If the phase A is disconnected, U2=-1/3UA.

(3) Add the phase currents of relays A, B, and C, respectively, and disconnect the other two phases from the relay and short-circuit the power supply to observe the relay action.

(4) Use the A, B, and C phase load currents to find the corresponding negative sequence current and phase, respectively. If the A-phase current, I2 = 1/3 (IA + a2IB + aIc) = 1/3 IA, similarly, when people B-phase current I2 = IB, through the human C-phase current I2 = Ic.

(5) Using the simulated U2 as a benchmark, draw the operating characteristic diagram of the negative sequence power direction relay, and then draw the negative sequence current obtained in item (4) to the characteristic diagram of the power direction relay to analyze the relay action. Happening. If the behavior of the relay is equal to the result of the analysis, the wiring is considered correct.如以断开A相电压求出的负序电压U2为基准绘出负序功率方向继电器的动作特性如图F-6所示(假设线路只送有功)。由图可知,分别通人A、C相电流继电器动作,通人B相电流时继电器不动作。继电保护知识问答汇编由扬州拓普电气科技有限公司生技部供稿,咨询热线51、如图F-7所示小接地电流系统中,k1(*近N侧)k2不同地点发生两点接地短路时,为什么横差方向保护会误动作?

答:如图F-7所示,k1点*近N侧且在M侧保护的相继动作区,N侧保护切除故障后,故障线路中还流有故障电流IKA,非故障线路中有故障电流Ikc。因此,M侧两线路保护的功率方向元件都会动作,横差方向保护将同时切除两条线路,造成非选择性误动作。

52、负序电流继电器在正常运行中,由于电流回路一相断线,此时负序电流与负荷电流的关系是什么?试分析之。

答:运行中负序电流继电器流过的电流为三相对称正序电流,当其电流回路一相断线时,流人继电器的电流为两相大小相等相位相差120'的电流,用对称分量法分析,其负序分量为I2=1/3(IA+a2IB+aIc)。如A相断线,则I2=-1/3IA,同理B相或C相断线时,则I2分别为-1/3IB,或-1/3IC,所以在电流回路一相断线时负序电流与负荷电流的关系为I2=-1/3Iph

53、方向阻抗继电器中引入极化电压为什么可以防止在保护安装处正方向发生三相金属性短路时的拒动?

答:方向阻抗继电器中极化回路,常用电容、电感、电阻元件串联,构成工频谐振回路。当保护安装处出口三相金属性短路时,由于电压突降为零,阻抗继电器因为无电压而可能拒动。但这时谐振回路内的电流将按50Hz频率逐渐衰减,在一定时间内,电压不致消失,以供给阻抗继电器必要的电压,保证其可*动作。

54、对发电机准同期并列的三个条件是怎样要求的?

答:对发电机准同期并列条件的要求为:

(1)待并发电机电压与系统电压应接近相等,其差值不应超过±(5%~10%)系统电压。

(2)待并发电机频率与系统频率应接近相等,其差值不应超过±(0.2%~0.5%)系统频率。

(3)并列断路器触头应在发电机电压与系统电压的相位差接近0°时刚好接通,故合闸瞬间该相位差一般不应超过±10°。

55、距离保护一段方向阻抗继电器为什么要加记忆回路,对记忆回路有什么要求?

答:距离保护一段方向阻抗元件如无记忆回路,当保护安装处出口发生三相金属性短路时,由于母线电压降到近于零,加到继电器端子上的电压也为零,此时保护将不能动作,从而出现了方向阻抗继电器的死区。为了清除死区,对方向阻抗继电器加装了记忆回路,正常时记忆回路处于谐振状态,当出口发生三相短路时,记忆回路按固有频率衰减,利用该衰减电压,保护继电器可*动作。对记忆回路的要求是,正常运行时经过记忆回路以后的极化电压与母线电压同相位,以保证继电器特性不变,因而回路应呈纯电阻性。短路以后希望回路自由振荡频率与系统频率一样,才能保证故障以后过渡过程中极化电压的相位也不变,一般对感应型阻抗继电器记忆时间不小于120ms,晶体管装置不小于50ms。

56、LFP-901A型保护和收发信机的连接与传统保护有何不同?

答:LFP-901A型保护中有完整的启动、停信、远方启动及每日交换信号操作的逻辑,收发信机只受保护控制传送信号。应特别注意不再利用传统的断路器的三相位置触点相串联接人收发信机的停信回路,收发信机远方启动应退出。LFP-90lA型保护和收发信机之间的连接采用单触点方式。

57、在试验时,当LFP-901A型保护装置中的重合闸不能充电时,应如何检查?

答:此时应做如下检查:

(1)根据LFP-900系列保护使用说明书,进入CPU2的开关量检查子菜单。

(2)检查下列开关量是否为如下状态:

HK=1TWJ=0HYJ=0BCH=0

(3)启动元件不动作。

(4)CPU2定值单上重合闸应投入,屏上切换把手不在停用位置。

58、微机继电保护装置的现场检验应包括哪些内容?

答:微机继电保护装置现场检验应做以下几项内容:

(1)测量绝缘。

(2)检验逆变电源(拉合直流电流,直流电压,缓慢上升、缓慢下降时逆变电源和微机继电保护装置应能正常工作)。

(3)检验固化的程序是否正确。

(4)检验数据采集系统的精度和平衡度(5)检验开关量输入和输出回路。

(6)检验定值单。

(7)整组试验。

(8)用一次电流及工作电压检验。

59、在装设接地铜排时是否必须将保护屏对地绝缘?

答:没有必要将保护屏对地绝缘。虽然保护屏骑在槽钢上,槽钢上又置有联通的铜网,但铜网与槽钢等的接触只不过是点接触。即使接触的地网两点间有由外部传来的地电位差,但因这个电位差只能通过两个接触电源和两点间的铜排电源才能形成回路,而铜排电源值远小于接触电源值,因而在铜排两点间不可能产生有影响的电位差。

60、综合重合闸对零序电流保护有什么影响?为什么?如何解决这一矛盾?

答:线路上装设综合重合闸装置,不可避免地将出现非全相运行,从而给系统的零序电流保护带来影响。这是因为,在非全相运行中会出现零序电流,造成保护误动。所以对动作机会较多的零序电流保护I段来说,为在非全相运行时不退出工作必须校验其整定值,许多情况下将定值抬高,从而缩短了其保护范围。为了解决这一矛盾,可以增设定值较大的不灵敏I段,在非全相运行中不拒切线路始端的接地故障。而灵敏I段定值较小,保护范围大,但在非全相运行时需退出工作。为了保证选择性,零序Ⅱ段动作时限应躲过第一次故障算起的单相重合闸周期,否则非全相运行时,应退出其运行,防止越级跳闸。故障线路的零序Ⅲ段的动作时限在重合闸过程中活当自动缩短。

61、为什么要求高频阻波器的阻塞阻抗要含有足够的电阻分量?

答:阻波器的作用是阻止高频信号电流外流,因为高频信号的外流必须要通过阻波器和加工母线对地阻抗串联才形成分流回路。而母线对地阻抗一般情况下是容抗,但也有可能是感抗,因此要求阻波器的阻塞阻抗要含有足够大的电阻分量,以保证即使阻塞阻抗的电抗分量正好同母线对地容抗相抵消时,阻波器也能有良好的阻塞作用。

62、超高压远距离输电线两侧单相跳闸后为什么出现潜供电流?对重合闸有什么影响?

答:文章阐述C相接地故障,两侧单相跳闸后,非故障相A、B仍处在工作状态。由于各相之间存在耦合电容C,,所以A、B相通过Cl向故障点k供给电容性电流Icl,同时由于各相之间存在互感,所以带负荷的A、B两相将在故障相产生感应电动势,该感应电动势通过故障点及相对地电容C。形成回路,向故障点供给一电感性电流,这两部分电流总称为潜供电流。由于潜供电流的影响,使短路处的电弧不能很快熄灭,如果采用单相快速重合闸,将会又一次造.持续性的弧光接地而使单相重合闸失败。所以单相重合闸的间,必须考虑到潜供电流的影响。

63、高频阻波器的工作原理是什么?

答:高频阻波器是防止高频信号向母线方向分流的设备。它是由电感和电容组成的并联谐振回路,调谐在所选用的载波频率,因而对高频载波电流呈现的阻抗很大,防止了高频信号的外流,对工频电流呈现的阻抗很小,不影响工频电力的传输。

64、耦合电容器在高频保护中的作用是什么?

答:耦合电容器是高频收发信机和高压输电线路之间的重要连接设备。由于它的电容量很小,对工频电流具有很大的阻抗,可防止工频高电压对收发信机的侵袭,而对高频信号呈现的阻抗很小,不妨碍高频电流的传送。耦合电容器的另一个作用是与结合滤过器组成带通滤过器。

66、画出双母线固定连接破坏后在完全差动保护区内、外故障时的电流分布图,并说明母线差动保护动作情况答:破坏双母线的固定连接后,保护区外故障,选择元件KAl、KA2均流过部分短路电流,但启动元件KA无电流,故母线差动保护不会动作。其电流分布,破坏双母线固定连接后,保护区内母线1故障时的电流分布。此时选择元件KAl、KA2均流过短路电流。选择元件KAl流过的短路电流大,动作切母联断路器及母线1上连接元件的断路器QFl、QF2。选择元件KA2流过的短路电流小,如不动作,则通过QF4仍供给短路电流,故障仍未消除。因此如破坏双母线固定连接,则必须将选择元件KAl、KA2触点短接,使母线差动保护变成无选择动作,将母线1、母线2上所有连接元件切除。

67、试述电流相位比较式母线保护的基本工作原理。

答:无论是电流差动母线保护还是比较母联断路器的电流相位与总差动电流相位的母线保护,其启动元件的动作电流必须避越外部短路时的最大不平衡电流。这在母线上连接元件较多、不平衡电流很大时,保护装置的灵敏度可能满足不了要求。因此,出现了电流相位比较式母线保护,其工作原理如下。文章阐述母线接线,当其正常运行或母线外部短路时,电流I1流人母线,

I2流出母线,它们的大小相等、相位相差180°。当母线上发生短路时,短路电流I1、I2均流向短路点,如果提供I1、I2的电源的电动势同相位,且I1、I2两支路的短路阻抗角相同时,I1、I2就同相位,其相位角差为0°。因此,可由比相元件来判断母线上是否发生故障。这种母线保护只反应电流间的相位,因此具有较高的灵敏度。

68、画出断路器灯光监视的控制、信号回路图.并说明其接线特点。

答:断路器灯光监视的控制、信号回路图,如图9—1所示。其接线特点如下。(1)控制开关SA采用LW2—2型。断路器的位置状态以红、绿灯表示。红灯亮表示断路器在合闸状态,并表示其跳闸回路完好;绿灯亮表示断路器在跳闸状态,并表示其合闸回路完好。合闸接触器KM的线圈电阻为249,(采用CZ。直流接触器),断路器跳闸线圈电阻一般为881'1。如果红、绿灯都不亮,则表示直流控制电源有问题,但此时不发音响信号。

(2)当自动同期或备用电源自动投入触点lAS闭合时,断路器合闸,红灯HR闪光;当保护动作,出口中间继电器KC触点闭合时,断路器跳闸,绿灯HG闪光,表明断路器实际位置与控制开关位置不一致。当断路器在合闸位置,其控制开关SAl—3、SAl7—19闭合,如此时保护动作或断路器误脱扣时,断路器辅助触点QF闭合,接通事故信号小母线WF回路,发出事故音响信号。

(3)断路器合闸和跳闸线圈的短脉冲,是*其回路串人的断路器的辅助触点QF来保证的。

(4)当控制开关SA在“预合”或“预分”位置时,指示灯通过SA9—10或SAl4一13触点接通闪光小母线(+)WH回路,指示灯闪光。

(5)断路器的防跳,由专设的防跳继电器KCF实现。

(6)由主控制室到操动机构间联系电缆的芯数为五芯。

69、新安装继电保护装置竣工后,验收的主要项目是什么?

答:新安装的保护装置竣工后,验收的主要项目如下:

(1)电气设备及线路有关实测参数完整正确。

(2)全部保护装置竣工图纸符合实际。

(3)装置定值符合整定通知单要求。

(4)检验项目及结果符合检验条例和有关规程的规定。

(5)核对电流互感器变比及伏安特性,其二次负载满足误差要求。

(6)屏前、后的设备应整齐、完好,回路绝缘良好,标志齐全、正确。

(7)二次电缆绝缘良好,标号齐全、正确。

(8)用一次负荷电流和工作电压进行验收试验,判断互感器极性、变比及其回路的正确性,判断方向、差动、距离、高频等保护装置有关元件及接线的正确性。

70、相差高频保护有何特点?

答:(1)在被保护线路两侧各装半套高频保护,通过高频信号的传送和比较,以实现保护的目的。扬州拓普电气科技有限公司认为它的保护区只限于本线路,其动作时限不需与相邻元件保护相配合,在被保护线路全长范围内发生各类故障,均能无时限切除。

(2)因高频保护不反应被保护线路以外的故障,不能作下-段线路的后备保护,所以线路上还需装设其他保护作本线及下一段线路的后备保护。

(3)相差高频保护选择性好、灵敏度高,广泛应用在110~220kV及以上高压输电线路上作主保护。

71、在大接地电流系统中,相间横差方向保护的直流操作电源为什么要采用零序横差方向保护来闭锁?

答:零序横差方向保护,采用零序电流和零序电压的复合起动元件,当平行线路外部相间故障时,零序电流、电压继电器均不动作。当内部相间故障时,零序电流继电器可能动作,但零序电压继电器不动作,相间横差方向电流保护不被闭锁。当平行线路内部发生接地短路时,零序电流、电压继电器均动作,闭锁相间横差方向保护,这样就避免了相间横差保护受非故障相电流影响而可能引起误动作。

72、电力系统在什么情况下运行将出现零序电流?试举出五种例子。

答:电力系统在三相不对称运行状况下将出现零序电流,例如:

(1)电力变压器三相运行参数不同。

(2)电力系统中有接地故障。

(3)单相重合闸过程中的两相运行。

(4)三相重合闸和手动合闸时断路器三相不同期投入(5)空载投人变压器时三相的励磁涌流不相等。

73、综合重合闸有几种运行方式?性能是什么?

答:综合重合闸可由切换开关实现如下四种重合闸方式:

(1)综合重合闸方式,功能是:单相故障,跳单相,单相重合(检查同期或检查无压),重合于永久性故障时跳三相。

(2)三相重合闸方式,功能是:任何类型的故障都跳三相,三相重合(检查同期或检查无压),重合于永久性故障时跳三相。

(3)单相方式,功能是:单相故障时跳单相,单相重合,相间故障时三相跳开不重合。

(4)停用方式,功能是:任何故障时都跳三相,不重合。

74、负序电流继电器,当其电抗变压器的两个一次绕组或二次绕组与中间变流器的绕组相应极性接反时,会产生什么结果?怎样防止?

答:负序电流继电器的电抗变压器两个一次绕组或二次绕组与中间变流器绕组的相应极性接反时,负序继电器将变为正序继电器。由此继电器构成的保护在投入运行后,尽管没有发生不对称故障,但只要负荷电流达到一定数值时,就会误动作。为保证负序电流继电器接线正确,防止出现上述情况,必须采取以下措施:

(1)通三相电源检查负序电流继电器的定值。

(2)用单相电源试验时,应按照负序滤过器的原理测量其相对极性,使之合乎要求,并须用负荷电流来检验,确认接线正确无误后,才投入运行。

75、直流两点接地为什么有时造成断路器误跳闸?有时造成断路器拒跳?有时造成熔丝熔断?

答:(1)两点接地可能造成断路器误跳闸:文章阐述所示,当直流接地发生在A、B两点时,将电流继电器1KA、2KA触点短接,而将KC起动,KC触点闭合而跳闸。A、C两点接地时短接KC触点而跳闸。在A、D两点,D、F两点等同样都能造成断路器误跳闸。(2)两点接地可能造成断路器拒动:接地发生在B、E两点E两点或C、E两点,断路器可能造成拒动。(3)两点接地引起熔丝熔断:接地点发生在A、E两点,引起熔丝熔断。当接地点发生在B、E和C、E两点,保护动作时,不但断路器拒跳,而且引起熔丝熔断,同时有烧坏继电器触点的可能。

76、负序功率方向继电器的灵敏角为什么定为-105°±10°?

答:负序功率方向继电器在继电保护装置中用以判断两相短路时负序功率方向。在电网中发生两相金属性短路(如BC两相短路)时,若以非故障相A相为基准,故障点的边界条件为Uk0=0,UkA1=UkA2=IkA1,IkA1=IkA2其相量图所示。当ZIΣ的阻抗角为75°时,即IkA1落后于UkA2为75°,而IkA2=-IkA1,即UkA2超前IkA2。因此为了使负序功率继电器灵敏、正确地判断负序功率方向,其最大灵敏角定为-105°±10°。

77、为什么大容量发电机应采用负序反时限过流保护?

答:负荷或系统的不对称,引起负序电流流过发电机定子绕组,并在发电机空气隙中建立负序旋转磁场,使转子感应出两倍频率的电流,引起转子发热。大型发电机由于采用了直接冷却式(水内冷和氢内冷),使其体积增大比容量增大要小,同时,基于经济和技术上的原因,大型机组的热容量裕度一般比中小型机组小。因此,转子的负序附加发热更应该注意,总的趋势是单机容量越大,A值越小,转子承受负序电流的能力越低,所以要特别强调对大型发电机的负序保护。发电机允许负序电流的持续时间关系式为A=I2t,I2越大,允许的时间越短,I2越小,允许的时间越长。由于发电机对I2的这种反时限特性,故在大型机组上应采用负序反时限过流保护。

78、发电机为什么要装设负序电流保护?

答:电力系统发生不对称短路或者三相不对称运行时,发电机定子绕组中就有负序电流,这个电流在发电机气隙中产生反向旋转磁场,相对于转子为两倍同步转速。因此在转子部件中出现倍频电流,该电流使得转子上电

Ship Building Steel Plate

Ship Building Steel Plate,Shipbuilding Plates,Shipbuilding Steel,Shipbuilding Steel Grades

Shandong Jianlong Special Steel Co., Ltd. , https://www.jianlongsteelpipe.com